Publication 1764-UM001B-EN-P - April 2002

Chapter

4

Communication Connections

This chapter describes how to set up communications for your control
system. The method you use and cabling required depend on your
application. This chapter also describes how the controller establishes
communication with the appropriate network. Topics include:

Default Communication Configuration

Communications Toggle Push Button

Connecting to the RS-232 Port

Connecting to a DH-485 Network

Connecting to DeviceNet

Connecting to Ethernet

Default Communication
Configuration

The MicroLogix 1500 has the following default communication
configuration.

ATTENTION

!

All devices communicating within a network, must
use the same protocol.

Table 4.1 DF1 Full-Duplex Configuration Parameters

Parameter

Default

Baud Rate

19.2K

Parity

none

Source ID (Node Address)

1

Control Line

no handshaking

Error Detection

CRC

Embedded Responses

auto detect

Duplicate Packet (Message) Detect

enabled

ACK Timeout

50 counts

NAK retries

3 retries

ENQ retries

3 retries

Stop Bits

1