Rockwell Automation 1764-xxxx MICROLOGIX 1500 PROGRAMMABLE CONTROLLERS User Manual

Page 149

Advertising
background image

Publication 1764-UM001B-EN-P - April 2002

System Loading and Heat Dissipation F-3

ensure that the maximum available 4K data table size will not be
exceeded. Refer to the 1769-SDN User Manual for more details.

4. Enter the current draw values in the “Calculated Current”

columns. Add up the current draw values to determine the
“SUBTOTAL2” values.

5. Verify that the total number of modules does not exceed the

system limits using the maximum values for the base unit and
Table F.5 for the expansion power supply, if used.

Table F.2 Selecting Hardware: Expansion I/O

Select I/O Modules for Each Bank:

Bus Current Draw
Specification (mA)

Calculate Current Draw:

Expansion I/O
Modules

Catalog Number

Base Unit
Expansion

(1)

Bank 1

(2)

Calculated Current for
Base Unit Expansion (mA)

Calculated Current for
Bank 1 Power Supply
(mA)

(3)

2250 mA max

400 mA max

n1

n2

X

Y

n1 x X

n1 x Y

n2 x X

n2 x Y

Number of Modules

(4)

at 5V dc

at 24V dc

at 5V dc

at 24V dc

at 5V dc

at 24V dc

1769-HSC

(5)

425

0

1769-IA16

115

0

1769-IA8I

90

0

1769-IF4 (Series A)

120

150

1769-IF4 (Series B)

120

60

1769-IF4XOF2

120

160

1769-IM12

100

0

1769-IQ16

115

0

1769-IQ6XOW4

105

50

1769-IR6

100

45

1769-IT6

100

40

1769-OA8

145

0

1769-OA16

225

0

1769-OB16

200

0

1769-OB16P

160

0

1769-OF2 (Series A)

120

200

1769-OF2 (Series B)

120

120

1769-OV16

200

0

1769-OW8

125

100

1769-OW8I

125

100

1769-OW16

205

180

1769-SDN

440

0

TOTAL MODULES:

SUBTOTAL2:

(A2)

(B2)

(C)

(D)

(1) May not exceed 8 I/O modules.

(2) No more than 8 I/O modules on either sid e of the power supply.

(3) Maximum value depends on the power supply chosen.

(4) Up to 16 modules may be used in a MicroLogix 1500 system when using a Series B Base Unit and Series C processor (up to 8 for Series A Base Units).

A maximum of 8 modules can be connected directly to the Base Unit.
A maximum of 8 modules can be connected to each side of the Expansion Power Supply.

(5) No more than 4 I/O modules may be connected to the base unit or to either side of the expansion power supply when the 1769-HSC or 1769-SDN are used in the system.