Publication GMSI10-UM005C-EN-P - May 2010

22 Installing the XM-320 Position Module

Connecting the Power Supply

Power supplied to the module must be nominally 24 Vdc (±10%) and must be
a Class 2 rated circuit.

Wire the DC-input power supply to the terminal base unit as shown in Figure
2.8.

Figure 2.8 DC Input Power Supply Connections

39

SetPtMult

Switch input to activate Set Point Multiplication (active closed)

40

Switch RTN

Switch return, shared between SetPtMult and Reset Relay

41

Reset Relay

Switch input to reset internal relay (active closed)

42

Reserved

43

24V Common

Internally DC-coupled to circuit ground

44

+24V In

Connection to primary external +24V power supply, positive
side

45

24V Common

Connection to external +24V power supply, negative side
(internally DC-coupled to circuit ground)

46

Relay N.C. 1

Relay Normally Closed contact 1

47

Relay Common 1

Relay Common contact 1

48

Relay N.O. 1

Relay Normally Open contact 1

49

Relay N.O. 2

Relay Normally Open contact 2

50

Relay Common 2

Relay Common contact 2

51

Relay N.C. 2

Relay Normally Closed contact 2

Terminal Block Assignments

No.

Name

Description

-

24V dc

Power

Supply

+

-