Publication GMSI10-UM005C-EN-P - May 2010

32 Installing the XM-320 Position Module

Connecting an LVDT

The following figures show the wiring from a linear variable differential
transformer (LVDT) to the terminal base unit of the XM-320.

Figure 2.20 LVDT to channel 1 wiring

ATTENTION

You may ground the cable shield at either end of the cable.
Do not ground the shield at both ends. Recommended
practice is to ground the cable shield at the XM-320
terminal base and not at the transducer. Any convenient
Chassis terminal may be used (see Terminal Block
Assignments on
page 20).

0

16

22

6

Signal Ground

+24V DC

Power Ground

Channel 1 Input Signal

Signal Ground

TYPICAL WIRING FOR LINEAR VARIABLE DIFFERENTIAL

TRANSFORMER (LVDT) TO XM-320 POSITION MODULE CHANNEL 1

Power Ground

Input Signal

+24V DC

Cable shield not
connected at this
end

37

Shield

43