Rockwell Automation 1440-TPS02-01RB XM-320 Position Module User Manual

Page 45

Advertising
background image

Publication GMSI10-UM005C-EN-P - May 2010

Installing the XM-320 Position Module 37

The DB-9 connector should be wired to the terminal base unit as
follows.

Mini-Connector - The mini-connector is located on the top of the
XM-320, as shown below.

Figure 2.25 Mini Connector

A special cable (Cat. No. 1440-SCDB9FXM2) is required for this
connection. The connector that inserts into the PC is a DB-9 female
connector, and the connector that inserts into the module is a USB
Mini-B male connector.

XM-320 Terminal Base Unit
(Cat. No. 1440-TB-B)

DB-9 Female Connector

TX Terminal (terminal 7) ----------------------

Pin 2 (RD - receive data)

RX Terminal (terminal 8) ----------------------

Pin 3 (TD - transmit data)

RTN Terminal (terminal 9) ---------------------

Pin 5 (SG - signal ground)

POSITION

1440-TPS02-01RB

mini-connector

WARNING

If you connect or disconnect the serial cable with power
applied to the module or the serial device on the other end
of the cable, an electrical arc can occur. This could cause an
explosion in hazardous location installations. Be sure that
power is removed or the area is nonhazardous before
proceeding.

IMPORTANT

If 24V Common is not referenced to earth ground, we
recommend you use an RS-232 isolator, such as Phoenix
PSM-ME-RS232/RS232-P (Cat. No. 1440-ISO-232-24), to
protect both the XM module and the computer.