Publication GMSI10-UM005C-EN-P - May 2010

72 Specifications

Heat Production

Transducer

Maximum: 5.28 Watts (18 BTU/hr)
Typical: 3.96 Watts (13.5 BTU/hr)

Isolated 24V dc, user configurable with
wiring

Environmental

Operating Temperature

Storage Temperature

Relative Humidity

-20 to +65°C (-4 to +149°F)

-40 to +85°C (-40 to +185°F)

95% non-condensing

All printed circuit boards are conformally coated
in accordance with IPC-A-610C.

Physical

Dimensions

Terminal Screw Torque

Height: 3.8in (97mm)
Width: 3.7in (94mm)
Depth: 3.7in (94mm)

7 pound-inches (0.6Nm)

Approvals
(when product or packaging is marked)

*See the Product Certification link at

www.rockwellautomation.com for Declarations
of Conformity, Certificates and other
certification details.

XM-320 Technical Specifications

Product Feature

Specification

UL

UL Listed for Ordinary
Locations

UL

UL Listed for Class I, Division 2
Group A, B, C, and D Hazardous
Locations

CSA

CSA Certified Process Control
Equipment

CSA

CSA Certified Process Control
Equipment for Class I, Division
2 Group A, B, C, and D
Hazardous Locations

EEX*

European Union 94/9/EEC ATEX
Directive, compliant with EN
50021; Potentially Explosive
Atmospheres, Protection “n”

CE*

European Union 89/336/EEC
EMC Directive

C-Tick*

Australian
Radiocommunications Act,
compliant with:
AS/NZS 2064, Industrial
Emissions