Basic Operations

Powering Up the Module

The XM-320 performs a self-test at power-up. The self-test includes an LED
test and a device test. During the LED test, the indicators will be turned on
independently and in sequence for approximately 0.25 seconds.

The device test occurs after the LED test. The Module Status (MS) indicator is
used to indicate the status of the device self-test.

Refer to Module Indicators on page 41 for more information about the LED
indicators.

Manually Resetting Relays

The XM-320 has an external reset switch located on top of the module, as
shown in Figure 2.27.

Figure 2.27 Reset Switch

MS Indicator State

Description

Flashing Red and Green

Device self test is in progress.

Solid Green or Flashing Green

Device self test completed successfully, and the
firmware is valid and running.

Flashing Red

Device self test completed, the hardware is OK, but the
firmware is invalid. Or, the firmware download is in
progress.

Solid Red

Unrecoverable fault, hardware failure, or Boot Loader
program may be corrupted.

POSITION

1440-TPS02-01RB

Press the Reset
Switch to reset the
relays