Rockwell Automation 1440-TPS02-01RB XM-320 Position Module User Manual
Page 39
Advertising
Publication GMSI10-UM005C-EN-P - May 2010
Installing the XM-320 Position Module 31
Figure 2.18 Non-contact sensor to channel 1 wiring
Figure 2.19 Non-contact sensor to channel 2 wiring
TYPICAL WIRING FOR NON-CONTACT SENSOR
TO XM-320 POSITION MODULE CHANNEL 1
COM
SIG
-24
Channel 1 Input Signal
-24V DC
0
16
22
6
Signal Common
Shield
Floating
37
Shield
Isolated Sensor Driver
43
TYPICAL WIRING FOR NON-CONTACT SENSOR
TO XM-320 POSITION MODULE CHANNEL 2
COM
SIG
-24
Shield
Channel 2 Input Signal
-24V DC
1
17
22
6
Signal Common
Shield
Floating
38
Isolated Sensor Driver
43
* See note
Note: If connecting non-contact sensors to both channels 1 and 2, install jumper between
terminals 17 and 43 instead of terminals 17 and 6 in order to limit wires to two per terminal.