Rockwell Automation 1440-TPS02-01RB XM-320 Position Module User Manual

Page 97

Advertising
background image

Publication GMSI10-UM005C-EN-P - May 2010

DeviceNet Objects 89

Instance 101 - Measurement Values

This is the default assembly instance that is sent using the I/O Poll Response
message when an I/O Poll Request is received from a DeviceNet Master.

Instance 199 - Dynamic Assembly

This Assembly instance can be created and configured with the XM Serial
Configuration Utility or RSMACC Enterprise Online Configuration Utility.
Using the configuration software, you determine the format of the data. This
assembly instance can be selected to be sent in response to an I/O Poll request
from a Master.

The dynamic Assembly can include all of the measurement values included in
Assembly instance 101. In addition, the dynamic Assembly can include the
following configuration parameters.

Table C.11 Instance 101 Data Format (Measurement Values Assembly)

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0 - 3

Transducer 1 Position value

4 - 7

Transducer 2 Position value

Table C.12 Instance 199 Component Mapping

EPATH (where ii =
instance number)

Class
Name

Class
Number

Instance
Number

Attribute
Name

Attribute
Number

Data
Type

21 1D 03 24 ii 30 04

Alarm

31D

h

1 - 2

Alarm Enable

4

BOOL

21 1D 03 24 ii 30 07

Alarm

31D

h

1 - 2

Condition

7

USINT

21 1D 03 24 ii 30 08

Alarm

31D

h

1 - 2

Alert Threshold (High)

8

REAL

21 1D 03 24 ii 30 09

Alarm

31D

h

1 - 2

Danger Threshold
(High)

9

REAL

21 1D 03 24 ii 30 0A

Alarm

31D

h

1 - 2

Alert Threshold Low

10

REAL

21 1D 03 24 ii 30 0B

Alarm

31D

h

1 - 2

Danger Threshold Low 11

REAL

21 1D 03 24 ii 30 0C

Alarm

31D

h

1 - 2

Hysteresis

12

REAL

21 1D 03 24 ii 30 0D

Alarm

31D

h

1 - 2

Threshold (Set Point)
Multiplier

13

REAL

21 1D 03 24 ii 30 0E

Alarm

31D

h

1 - 16

Startup Period

14

UINT

21 23 03 24 ii 30 04

Relay

323

h

1 - 5

Relay Enable

4

BOOL

21 23 03 24 ii 30 05

Relay

323

h

1 - 5

Latch Enable

5

BOOL

21 23 03 24 ii 30 06

Relay

323

h

1 - 5

Failsafe Enable

6

BOOL

21 23 03 24 ii 30 07

Relay

323

h

1 - 5

Delay

7

UINT

21 23 03 24 ii 30 09

Relay

323

h

1 - 5

Alarm Level

9

BYTE

Advertising