DeviceNet Information 81

An XM module will enter Run mode automatically after the ADR
scanner restores the module’s configuration only if the module is in Run
mode at the time the configuration is saved to the scanner. If the
module is in Program mode when the configuration is saved, then the
module will remain in Program after the configuration is downloaded by
the ADR scanner.

The ADR scanner saves and restores only the configuration parameters
contained in the module’s EDS file. Some XM parameters are not
included in the EDS file because they are not supported by either the
EDS specification or the tools that read the EDS files, for example
RSNetWorx for DeviceNet. These configuration parameters will not be
restored with ADR.

Below is a list of the configuration parameters that are not included in
the EDS file and can not be saved or restored with ADR.

Channel Name
Tachometer Name
Alarm Name
Relay Name
All Triggered Trend related parameters (see page 63)
All SU/CD Trend related parameters
Custom Assembly structure (see page 65)

The ADR and trigger group functions cannot be used together. A
module can have only one primary master so a module cannot be both
configured for ADR and included in a trigger group. The ADR scanner
must be the primary master for the modules configured for ADR. The
XM-440 Master Relay module must be the primary master for modules
included in a trigger group.