Module indicators, Module status (ms) indicator – Rockwell Automation 1440-TPS02-01RB XM-320 Position Module User Manual

Page 49

Advertising
background image

Publication GMSI10-UM005C-EN-P - May 2010

Installing the XM-320 Position Module 41

Module Indicators

The XM-320 has six LED indicators, which include a module status (MS)
indicator, a network status (NS) indicator, a status indicator for each channel
(CH1 and CH2), an activation indicator for the Setpoint Multiplier, and a
status indicator for the Relay. The LED indicators are located on top of the
module.

Figure 2.26 LED Indicators

The following tables describe the states of the LED status indicators.

Module Status (MS) Indicator

1

Program Mode - Typically this occurs when the module configuration settings are being updated with the XM
Serial Configuration Utility. In Program Mode, the module does not perform its usual functions. The signal
processing/measurement process is stopped, and the status of the alarms is set to the disarm state to prevent
a false alert or danger status.

2

Run Mode - In Run Mode, the module collects measurement data and monitors each measurement device.

POSITION

1440-TPS02-01RB

Module Indicators

Color

State

Description

No color

Off

No power applied to the module.

Green

Flashing Red

Module performing power-up self test.

Flashing

Module operating in Program Mode

1

.

Solid

Module operating in Run Mode

2

.

Red

Flashing

Application firmware is invalid or not loaded.
Download firmware to the module.

Firmware download is currently in progress.

The module power voltage is incorrect.

Solid

An unrecoverable fault has occurred. The module may
need to be repaired or replaced.

Advertising