36 Installing the XM-320 Position Module

Figure 2.24 Non-contact sensor and LVDT wiring

PC Serial Port Connection

The XM-320 includes a serial port connection that allows you to connect a PC
to it and configure the module’s parameters. There are two methods of
connecting an external device to the module’s serial port.

Terminal Base Unit - There are three terminals on the terminal base
unit you can use for the serial port connection. They are TxD, RxD, and
RTN (terminals 7, 8, and 9, respectively). If these three terminals are
wired to a DB-9 female connector, then a standard RS-232 serial cable
with 9-pin (DB-9) connectors can be used to connect the module to a
PC (no null modem is required).

0

16

22

6

Signal Ground

TYPICAL WIRING FO R NON-CONTACT SENSOR AND LINEAR VARIABLE

DIFFERENTIAL TRANSFORMER (LVDT) TO XM-320 POSITION MODULE

Power Ground

Input Signal

+24V DC

SIG

-24

COM

Shield

Channel 1 Input Signal

-24V DC

Signal Common

17

1

25

28

Signal Ground

Channel 2 Input Signal

+24V DC

Power Ground

Cable shield not
connected at this
end

Shield Floating

37

Shield

Isolated Sensor Driver

38

Advertising