34 Installing the XM-320 Position Module
Figure 2.22 Cam potentiometer to channel 1 wiring
Figure 2.23 Cam potentiometer to channel 2 wiring
TYPICAL WIRING FOR CAM (VALVE) POTENTIOMETER
T O X M - 3 2 0 P O S I T I O N M O D U L E C H A N N E L 1
Signal
Common
+24V DC
Channel 1
Input Signal
0
16
22
6
Channel 1 Input Signal
Signal Common
+24V DC
Cable shield
not connected
at this end
37
Shield
28
TYPICAL WIRING FOR CAM (VALVE) POTENTIOMETER
T O X M - 3 2 0 P O S I T IO N M O D U L E C H A N N E L 2
Signal
Common
+24V DC
Channel 2
Input Signal
1
17
22
6
Channel 2 Input Signal
Signal Common
+24V DC
Cable shield
not connected
at this end
38
Shield
28
* See note
Note: If connecting cam potentiometers to both channels 1 and 2, install jumper between