Configuration Parameters 53

Calculate and set the transducers as follows:

1. To determine the placement of Probe A, add the Cold Set Point to the

Transducer Offset, then add the Axial Position from the Active Face.

2. To determine the placement of Probe B, subtract the Cold Set Point

from the Full Scale Reading, then add the Transducer Offset and the
Axial Position from the Active Face.

3. Enter the following data on the Channels property page in the XM-320

Position Module Configuration Tool.

1

This value is .2 volts below the lowest voltage the transducer will output for this measurement taken from the
calibration chart.

2

This value is .2 volts above the highest voltage the transducer will output for this measurement taken from the
calibration chart.

Channel 1 (Probe A)

Channel 2 (Probe B)

Sensitivity

30

Sensitivity

30

Eng. Units

mils

Eng. Units

mils

Output Data Unit

mils

Output Data Unit

mils

Fault Low

-18

1

Fault Low

-18.2

1

Fault High

-2.6

2

Fault High

-2.8

2

DC Bias Time Constant

1

DC Bias Time Constant

1

Target Angle

90

Target Angle

90

Upscale

Away

Upscale

Towards

Calibration Offset

250

Calibration Offset

1000

Calibration Bias

Press
Calculate
Bias

Calibration Bias

-33 (You
must enter
value using
formula
below)

Mode

Head-to-Head

Probe A Gap

250 150 0

400 mils

=

+

+

=

Probe B Gap

1000 250 150 0

+

+

900

=

=