Connecting the transducer – Rockwell Automation 1440-TPS02-01RB XM-320 Position Module User Manual

Page 38

Advertising
background image

Publication GMSI10-UM005C-EN-P - May 2010

30 Installing the XM-320 Position Module

Figure 2.17 4-20mA Output Connections

Connecting the Transducer

The XM-320 will accept signals from a linear variable differential transformer
(LVDT), non-contact eddy current probe, or a rotary cam (valve)
potentiometer.

Connecting a Non-contact Sensor

The following figures show the wiring from a non-contact sensor to the
terminal base unit of the XM-320 module.

ATTENTION

The 4-20mA outputs are functionally isolated from other
circuits. It is recommended that the outputs be grounded at
a single point. Connect the 4-20mA (-) to the XM terminal
base (Chassis terminal) or directly to the DIN rail, or
ground the signal at the other equipment in the 4-20mA
loop.

ATTENTION

You may ground the cable shield at either end of the cable.
Do not ground the shield at both ends. Recommended
practice is to ground the cable shield at the XM-320
terminal base and not at the transducer. Any convenient
Chassis terminal may be used (see Terminal Block
Assignments on
page 20).

Advertising