Publication GMSI10-UM005C-EN-P - May 2010

70 Specifications

Outputs

4-20mA Outputs

Buffered Outputs

Two isolated outputs
600 ohm max load

2 outputs; 1 per channel

Indicators

6 LEDs Module Status - red/green

Network Status - red/green
Channel 1 Status - yellow/red
Channel 2 Status - yellow/red
Setpoint Multiplier - yellow
Relay - red

Measurement Modes

Normal (two independent channels)
Head-to-head
Radial cancel

Delta Time Buffer

Number of Records

Delta Time Interval

Trigger Mode

2048

1 to 3600 seconds

Relay on the XM-320 module is activated,
or by a trigger event (for example,
DeviceNet command from a controller or
host)

The data collected in the buffer is user
configurable.

Alarms

Number

Operators

Hysteresis

Startup Inhibit/Setpoint Multiplication

2 alarm and danger pairs

Greater than
Less than
Inside range
Outside range

User configurable in software

Period: 0 to 1092 minutes, adjustable in 0.1
minute increments
Inhibit/multiplication function: Multiply by
N (0 to 10, 0 = Disarm)

Relays

Number Single on-board relay, two sets of contacts -

DPDT (2 Form C)
Four additional relays when interconnected
to an XM-441 Expansion Relay module, or
Four virtual relays whose status can be
used by remote Control Systems or the
XM-440 Master Relay module

XM-320 Technical Specifications

Product Feature

Specification