Publication GMSI10-UM005C-EN-P - May 2010

60 Configuration Parameters

Sets the alarm conditions that will cause the relay to
activate. You can select more than one.

Normal - The current measurement is not in
excess of any alarm thresholds.

Alert - The current measurement is in excess of
the alarm level threshold(s) but not in excess of the
danger level threshold(s).

Danger - The current measurement is in excess of
the danger level threshold(s).

Disarm-The alarm is disabled or the device is in
Program mode.

Xdcr Fault - A transducer fault is detected on the
associated transducer.

Module Fault - Hardware or firmware failure, or
an error has been detected and is preventing
proper operation of the device.

Options: Normal

Danger
Xdcr Fault
Alert
Disarm
Module Fault

Check means enable.
Clear means disable.

Relay Installed

Indicates whether the relay is a physical relay on a
module or a virtual relay. If the relay is a physical
relay, then you can set the Failsafe parameter.

If the relay is a virtual relay, the Failsafe parameter
is not used or it is disabled.

Relay Parameters

Parameter Name

Description

Values/Comments

XM Configuration
Utility

EDS File

Alarm Status to
Activate On

Alarm Levels

XM Configuration
Utility

EDS File

Check = Physical
Relay

Installed =
Physical Relay

Clear = Virtual Relay Not Installed =

Virtual Relay