Publication GMSI10-UM005C-EN-P - May 2010

Specifications 71

On-board Relay Rating

Failsafe

Latching

Time Delay

Voting Logic

Reset

Activation On

Maximum Voltage: 125V dc, 125V ac
Maximum Current: 3.5A*
Minimum Current: 0
Maximum Power: 60W, 62.5VA

*Max current is up to 40°C, then derates to 2A at

65°C.

Agency Rating:
120V ac @ 0.5A
110V dc @ 0.3A
30V dc @ 1.0A

Normally energized (failsafe), or
Normally de-energized (non-fail-safe)

Latching, or
Non-latching

0 to 25.5 seconds, adjustable in 100msec
increments

Single or paired "And" or "Or" logic applied
to any alarm

Local reset switch on top of module
Remote reset switch wired to terminal base
Digital reset command via serial or
DeviceNet interface

Alarm Status:

Normal
Alert
Danger
Disarm
Transducer fault
Module fault

Non-Volatile Configuration

A copy of the module configuration is
retained in non-volatile memory from where
it is loaded upon power up*.

*The configuration stored in non-volatile

memory can be deleted only by a module-reset
command sent via the serial interface, using
the Serial Configuration Utility, or via
DeviceNet from any compliant software
application.

Power

Module

Consumption

+21.6 to 26.4V dc

Maximum: 200mA
Typical: 165mA

XM-320 Technical Specifications