Rockwell Automation 1440-TPS02-01RB XM-320 Position Module User Manual

Page 55

Advertising
background image

Publication GMSI10-UM005C-EN-P - May 2010

Configuration Parameters 47

DC Bias Time Constant

The time constant used for exponential averaging
(low pass filtering) of the transducer DC bias
measurement. The corner frequency for the low pass
filter is 1 / (2

π

x DC Bias Time Constant). The

greater the value entered, the longer the settling
time of the measured value to a change in the input
signal. See example table below.

Seconds

Target Angle

Sets the angle between the shaft and the target
surface. The target surface moves with the shaft.
The transducer is mounted perpendicular to the
target surface.

degrees

Upscale

Sets the movement of the target relative to the
transducer that is considered positive displacement.

Options: Away

Towards

Calibration Offset (XM Serial
Configuration Utility only)

Enter the position of the current Transducer DC
Bias
reading.

mils

Channel Parameters

Parameter Name

Description

Values/Comments

Time Constant
(seconds)

-3dB Frequency
(Hz)

Settling
(seconds)

1

0.159

2.2

2

0.080

4.4

3

0.053

6.6

4

0.040

8.8

5

0.032

11

6

0.027

13.2

7

0.023

15.4

8

0.020

17.6

9

0.018

19.8

10

0.016

22