Publication GMSI10-UM005C-EN-P - May 2010

24 Installing the XM-320 Position Module

Figures 2.9 and 2.10 illustrate the behavior of the NC and NO terminals when
the relay is wired for failsafe, alarm or nonalarm condition or non-failsafe,
alarm or nonalarm condition.

IMPORTANT

T

The NC/NO terminal descriptions (page 22) correspond
to a de-energized (unpowered) relay.

When the relay is configured for non-failsafe operation, the
relay is normally de-energized.

When the relay is configured for failsafe operation, the
relay is normally energized, and the behavior of the NC and
NO terminals is inverted.

Table 2.1 Relay Connections for XM-320

Configured for

Failsafe Operation

Relay 1 Terminals

Nonalarm

Alarm

Wire Contacts

Contact 1

Contact 2

Closed Opened

COM

47

50

NO

48

49

Opened

Closed

COM 47

50

NC

46

51

Configured for

Non-failsafe Operation

Relay 1 Terminals

Nonalarm

Alarm

Wire Contacts

Contact 1

Contact 2

Closed

Opened

COM

47

50

NC

46

51

Opened

Closed

COM

47

50

NO

48

49