Use and Specifications 2-3

Max. outer inductivities allowed

2 mH

1 mH

0.5 mH

0.2 mH

Max. outer capacities allowed

380 nF

430 nF

510 nF

660 nF

Sensor connections

Ignition protection type intrinsically-safe

EEx ia IIB

Clamps D1...D5, E1...E5

for connection of accompanying sensors only

F1...F5, G1...G5

Type POA/...OCL/... according to TÜV 03

ATEX

2262

Max.

values

per

circuit:

U

0

= 10.5 V

I

0

= 640 mA

rectangular

characteristic

Max.

outer

inductivities

allowed:

0.12

mH

Max.

outer

capacities

allowed: 4.8

µF

The intrinsically-safe circuits are isolated galvanically safe from the remaining
circuits up to a peak voltage of 375 volts.

The certification is valid only when the corresponding label exists
on the transmitter or sensor nameplate.

For installation and initial start-up, perform all work in
accordance with the appropriate certificates of conformity and
testing from the respective authorities.