Diagnosis

PSSnet SHL - Web- based Interface

Pilz GmbH & Co. KG, Felix- Wankel Str. 2, 73760 Ostfildern

7.6 Signal contact

127

…

In the “Mode Signal contact” field, you select the “Monitoring correct op-
eration” mode. In this mode the signal contacts monitor the functions of
the device, thus enabling remote diagnosis.
A break in contact is reported via the potential-free signal contact (relay
contact, closed circuit):

X

Voltage supply 1/2 failure or continuous device malfunction (internal volt-
age). Select “Monitor” for the power supply if the signal contact should re-
port the failure of the voltage supply or the internal 3.3 VDC voltage.

X

The temperature threshold has been exceeded or has not been reached

(see on page

17 „System data“)

. Select “Monitor” for the temperature if

the signal contact should report an impermissible temperature.

X

Removing a module. Select “Monitor” for removing modules if the signal
contact is to report the removal of a module (for modular devices).

X

Fan failure (for devices with a fan).

X

The removal of the SCA. Select “Monitor” for SCA removal if the signal
contact is to report the removal of an SCA (for devices which support the
SCA).

X

The defective link status of at least one port. The reporting of the link sta-
tus can be masked via the management for each port in the device. Link
status is not monitored in the state on delivery. Select “Monitor” for con-
nection errors if the signal contact is to report a defective link status for at
least one port.

X

Redundancy failure in the redundant ring

(see on page

108

„Ring

Redun-

dancy“)

. Select “Monitor” for the ring redundancy if the signal contact is to

report a redundancy that no longer exists in the redundant ring.

X

Error in the Ring/Network coupling. Select “Monitor” for the Ring/Network
coupling if the signal contact is to report an error in the Ring/Network
coupling

(see on page

116 „Preparing a Ring/Network coupling“)

.

In RM mode, the device also signals the following state:

X

Redundancy existing. State on delivery: ring redundancy is not
monitored.