Alarms (traps), 7 alarms (traps) – Pilz PSSnet SHL 8T MRP User Manual

Page 129

Advertising
background image

Diagnosis

PSSnet SHL - Web- based Interface

Pilz GmbH & Co. KG, Felix- Wankel Str. 2, 73760 Ostfildern

7.7 Alarms (Traps)

129

7.7 Alarms (Traps)

This dialog allows you to determine which events trigger an alarm (trap) and
where these alarms should be sent.

…

Select „Create entry“.

…

In the „Address“ column, enter the IP address of the management station
to which the traps should be sent.

…

In the „Enabled“ column, you mark the entries which should be taken into
account when traps are being sent.

…

In the „Selection“ frame, select the trap categories from which you want
to send traps.

The events which can be selected are:

Name

Meaning

Authentication

The device has rejected an unauthorized access attempt,

(see on page

42

„SNMPv1/v2 Access Settings“)

,

(see on page

140 „Port Mirroring“)

.

Link Up/Down

At one port of the device, the link to a device connected there has been es-
tablished/interrupted.

Spanning Tree

The topology of the Rapid Spanning Tree has changed.

Chassis

Summarizes the following events:
– The status of a supply voltage has changed (see the System dialog).
– The status of the signal contact has changed.
To take this event into account, you activate “Create trap when status
changes” in the Diagnostics:Signal Contact 1/2 dialog.

– A media module was added or removed.
– The AutoConfiguration AdapterSCA was added or removed.
– The temperature threshold was exceeded/not reached.
– The receiver power status of a port with an SFP module has changed (see
dialog Dialog:Ports:SFP Modules).

Redundancy

The redundancy status of the ring redundancy (redundant line active/inac-
tive) or the redundant Ring/Network coupling (redundancy exists) has
changed.

Port security

On one port a data packet has been received from an unauthorized terminal
device (see the Port Security dialog).

Table 45: Trap categories

Advertising
This manual is related to the following products: