F-4000 Series Ultrasonic Flow Meter Manual 05/15 - 0707-13 / 18838

Page 12

CAUTION

Do not drill additional holes in this enclosure. Doing so may damage the electronic circuitry

contained within and will void all warranties.

!

IMPORTANT NOTE

This ONICON F-4000 Ultrasonic Flow Meter is a custom calibrated system. Unless specifically

noted in writing by ONICON, ALL COMPONENTS (electronics enclosure and precision matched

transducers) share the same serial number and must be installed together as a system. Mixing

components from different systems will result in significant errors in calibration.

i

3.3 MECHANICAL INSTALLATION

3.3.1 Mounting the Enclosure


Find an easily accessible location where electrical connections can be made and meter
readings can be taken from the floor level. Mount the enclosure on a vibration-free
surface. Avoid sites such as the plenum of a fan coil, heat exchanger, or other housings
containing motors. Avoid mounting the enclosure in close proximity to VFD’s, electric
motors or other strong sources of electrical interference.

6”

2.5”

10.75”

Hinge side shown

for refernce.

2.5”

2”

4”

4xØ0.312

2xØ1.115

2”

2”

4”

2xØ1.115