ONICON F-4000 Series User Manual

Page 40

Advertising
background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • [email protected]

F-4000 Series Ultrasonic Flow Meter Manual 05/15 - 0707-13 / 18838

Page 40

ANALOG VALUE OBJECT Properties

Property Identifier

Description and/or Example

R/W

Object_Identifier

Unique identifier number

R

Object_Type

2 – Analog Value

R

Present_Value

Real (Floating point) Number

R

Description

Character string representing engineering units (e.g. GAL/MIN)

R

Units

No-units (95)

R

Status_Flags

IN_ALARM,FAULT,OVERRIDDEN,OUT_OF_SERVICE (e.g. 0,0,0,0)

R

Event_State

0 - NORMAL

R

Out_Of_Service

0 - FALSE

R

BINARY VALUE OBJECTS

BACnet Object

Description

BV0

Totalizer reset (Read/Write)

BV1

Spacing alarm (Read only)

BV2

Empty alarm (Read only)

BV3

Rate alarm(Read only)

BV4

Fault alarm (Read only)

BV5

Aeration alarm (Read only)

BV6

Memory alarm (Read only)

BV7

Makeup alarm (Read only)

BV8

Interface alarm (Read only)

BV9

Pig alarm (Read only)

BV10

Zeromatic alarm (Read only)

BINARY VALUE OBJECT Properties

Property Identifier Description and/or Example

R/W

Object_Identifier

Unique identifier number

R

Object_Type

5 – Binary Value

R

Present_Value

Binary (e.g. 0 or 1)

R/W*

Description

Character string representing object function (e.g. Aeration Alarm)

R

Priority_Array

Manual Operator (8)

R

Status_Flags

IN_ALARM,FAULT,OVERRIDDEN,OUT_OF_SERVICE (e.g. 0,0,0,0)

R

Event_State

NORMAL

R

Out_Of_Service

FALSE

R