Point-To-Point, modem, (Clause 10), baud rate(s):

o

LonTalk, (Clause 11), medium:

o

BACnet/ZigBee (ANNEX O)

o

Other:

Device Address Binding:
Is static device binding supported? o Yes þ No
Networking Options:

o

Router, Clause 6 - List all routing configurations, e.g., ARCNET-Ethernet, Ethernet- MS/TP, etc.

o

Annex H, BACnet Tunneling Router over IP

5.4

Modbus

Modbus is a commonly used protocol for communication in supervisory and data acquisition
(SCADA) applications. It uses registers to address data which can be formatted in various types
including, REAL, INTEGER, & BOOLEAN (coils).

The following Modbus Function Codes are supported:

Function Code

Name

Description

1

Read Coil(s)

Read one or more coil present values (0 or 1)

2

Read Discreet Input(s)

Read one or more discreet input present values (0 or 1)

3

Read Holding Register(s)

Read one or more holding register present values

4

Read Input Register(s)

Read one or more input register present values

5

Write Single Coil

Write (0 or 1) to a single coil

6

Write Single Register

Write to a single holding register

15

Write Multiple Coils

Write (0 or 1) to multiple coils

16

Write Multiple Registers

Write to a multiple holding registers

Memory Map

Alarm Status Input Register (Read Only)

Description

Address

Register Type

Bytes

Data Type

Example

Alarm Status

295

Input Register

16

String

__ERF___

Data Entry Holding Registers (Read & Write)

Description

Address

Register Type

Bytes

Data Type

Example

Aeration Alarm Level

1115

Holding Register

2

Integer

50

Batch Sample Total

1107

Holding Register

4

Real

10.0

Deadband Control

1105

Holding Register

4

Real

0.0

Hi Flow Alarm Level

1109

Holding Register

4

Real

100.0

Lo Flow Alarm Level

1111

Holding Register

4

Real

10.0

Slew Mode Selection

1101

Holding Register

2

Real

1

Smart Slew

1104

Holding Register

2

Integer

6

Time Average

1102

Holding Register

4

Real

10.0

Vs Alarm Level

1113

Holding Register

4

Real

2100.0