19 exit – Watson-Marlow 620U User Manual

Page 55

Advertising
background image

Watson-Marlow 620UN, 620U, 620SN, 620S User Manual

55

Make a selection using the UP or DOWN keys and press ENTER to confirm your
choice.

The information on pin outs duplicates the details described in this instruction man-
ual under Automatic control wiring.

The screens available are all presented in a similar manner. For example, on select-
ing Analogue input, the following screen is displayed:

This indicates that the analogue input signal must be applied to pin 4 of the lower
D-connector at the rear of the pump, where 0 volts is available on pin 16. If the ana-
logue input is configured for a 4-20mA signal, the maximum permitted voltage is 5
volts; if the analogue input is configured for a 0-10V or 1-5V signal, the maximum
permitted voltage is 10 volts.

The information available on selecting Supply and Others is presented on two
screens each. Pressing DOWN when the first screen of each is displayed causes the
second screen to appear. UP performs a similar function.

Pressing STOP or ENTER in any Pin out information screen returns the user to the
appropriate Pin out menu screen.

To leave the Pin out menu screens

Cycle through the Pin out menu screens until the fifth screen is displayed. Select
Exit using the UP or DOWN keys and press ENTER to confirm your choice.

Alternatively ...

Repeatedly press STOP to go back level by level until the main menu is displayed.