3 logic output 3, 4 logic output 4 – Watson-Marlow 620U User Manual

Page 74

Advertising
background image

Watson-Marlow 620UN, 620U, 620SN, 620S User Manual

74

21.9.3 Logic output 3

Output 3 is taken from pin 13 of the upper D-connector, depending on the logic state
of the function assigned to Output 3. Alternatively, a load such as a relay coil may
be connected to pin 13, ground to pin 17. Current will flow through the circuit
depending on the logic sate of the function assigned to Output 3. Do not connect to
any device requiring more than 50mA.

By default, output 3 is configured to indicate Auto/Man status. See 12 Switching the
pump on for the first time
.

21.9.4 Logic output 4

Output 4 is taken from pin 12 of the upper D-connector, depending on the logic state
of the function assigned to Output 4. Alternatively, a load such as a relay coil may
be connected to pin 12, ground to pin 17. Current will flow through the circuit
depending on the logic state of the function assigned to Output 4. Do not connect
to any device requiring more than 50mA.

By default, output 4 is configured to indicate General alarm status. See 12 Switching
the pump on for the first time
.