CHAPTER 8

ANALOG I/O

8-1

Figure 8-1 Analog connectors and jumpers

CHAPTER SYNOPSIS

Ž

Brief description of analog input capabilities

Ž

Acquir ing analog da ta

Ž

High voltage interfacing

Ž

Conve rting analo g reading s to real w orld units

Ž

Calibration

Ž

Analog output discussion

Ž

4-20 mA output

Ž

Analog po wer su pply

DESCRIPTION

ANALOG I/O CH APTER 8

The RPC-2350 has eight single ended or four differential
analog input channels than can be interfaced to external
analog devices. These channels can be used to measure
voltages from tr ansducers, 4-20 mA. current loops,
thermistors, etc. The conver ter reads a voltage and
retur ns a 12 bit (4096 count) num ber in und er a m illi-
second. Inputs are progr ammable for 0 to + 5 or ±2.5
volt, single ended or differential mode.

Additionally, 2 analog outpu t channels w ith 12 bit
accuracy are optionally available. Output voltage is 0-
5V, 0-10V , or ±5V. Outputs can drive optional 4-20
mA. current loops.

Filter capacitors may be added to pads designated as
W13. T his can reduce noise on analog inputs. Values
are app lication depend ent. 0.01 mfd is a goo d value to
start fro m. Higher values ma y be used in ex trem ely
noisy envir onmen ts or wh en time be tween sam ples is
long (> 100 ms).

Input impedance is 100K ohm to ground. Inputs are

protected to ±12V. Readings on other channels are
affected when one channel is over range.

Conve rsion tim e is under 500 micr o-seconds/ channel.

AIN function is used to return a voltage while AOT
writes an output voltage.

This chapter begins with basic hook-up information, then
proceeds to initialization, data reading, and calibration.
Analog output option is discussed near the end.

Analog output 1 (AOT 1) may optionally provide
software contrast control for the LCD graphics display.
When it is used for this purpose, 4-20 Ma output or
other voltage output may not be used.

CONNECTING ANALOG I/O

Analog I/O interface via J7. The STB-20 terminal board
may be used to br ing signals to terminal blocks.

The following table defines the signal pin out from
analog I/O port J7.

J7 Pin #

Signal

1

CH0 input

2-16

Ground (e ven pins)

3

CH1 input

5

CH2 input

7

CH3 input

9

CH4 input

11

CH5 input

13

CH6 input

15

CH7 input

17

DAC 0 output

18

+ 12V

19

DAC 1 output (also gr aphics contr ast)

20

-12V

Advertising