Chapter 8 analog i/o – Remote Processing RPC-2350 User Manual

Page 49

Advertising
background image

CHAPTER 8

ANALOG I/O

8-7

Figure 8-5 Cur rent loop IC’s & connector

Current loop power
The cur rent outpu t IC' s requir e at least 12V DC to
operate . T he interna l + 12V supp ly may be used. It is
available at J12 -1. C onnect J12-1 to J12-4 and/ or -8 to
use the internal supply.

When runs are long using small gauge wire you may
need to use an externa l + 18V to + 30V D C supply to
power the curr ent loop. If this supply is also use d to
power the board, you can optionally connect current loop
input power pins CLP 0 and/or C LP1 (J12-4 and J12-8)
to J12-6. This pin also goes to P2-4.

ANALOG POWER SUPPLY

The RPC -2350 generates its own power for RS-232,
LCD display, and analog I/O. Unregulated ± voltages
are available at J7, pins 18 (+ 12V) and 20 (-12V).

+ 12V outpu t can supply ab out 45 mA . of c urre nt total.
Subtrac t 20 mA . for each 4-20 m A. output.

-12V output can supply about 15 m A. The D/ A’s use
some current (1 mA.)

COMMANDS

The following is a list of CAMBASIC com mands for
analog input an d output.

Command

Function

CON FIG AIN

Configures analog input for
voltage range and mode.

AIN

Returns result of reading for
a channel

AOT

Sends value to D/A converter

Use the table below to allocate input channels for your
application.

J7 Pin

#

Analog

input

channel

Description/ use

x

n

0-5V, pressure

1

0

3

1

5

2

7

3

9

4

11

5

13

6

15

7

Advertising