Sanyo DHX4852 User Manual

Page 113

Advertising
background image

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

3-65

Control of W-2WAY ECO-i SYSTEM

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

6. Remote Sensor

How to Install the Remote Sensor

< NOTE 1 > Do not twist the remote sensor wiring with the power wiring or run it in the same metal conduit,

because this may cause malfunction.

< NOTE 2 > Install the remote sensor away from sources of electrical noise.
< NOTE 3 > Install a noise filter or take other appropriate action if electrical noise affects the power supply

circuit of the unit.

Use an electric junction box (supplied locally) (Fig. 3-43) for flush mounting of the remote sensor.

Fig. 3-43

Simplified remote controller

Under case (back case)

Spacer

Machine screws
M4

×

25 or 5/32”

×

1”

Electric junction box
for one box (no cover)

Wall

Fig. 3-44

1. Insert a screwdriver or the like in the groove on the lower side of the remote sensor body to pry off the

back case. (Fig. 3-44)

2. Use the 2 supplied M4 or 5/32" machine screws to secure the remote sensor back case. Prior to

mounting, clear the cutouts in the back case corresponding to the holes in the wall box using a screw-
driver or the like. Use the spacers and take care not to tighten the screws excessively. If the back case
will not seat well, cut the spacers to a suitable thickness.

3. Connect locally supplied 2 core lead wires to the lead wires from the remote sensor. (See “How to wire

the remote sensor.”)
When connecting the locally supplied 2 core lead wires to the terminal block, check the termi-
nal numbers in the indoor unit to make sure that the wires are correctly connected. (Fig. 3-45)
(The remote sensor is damaged if 208 / 230V AC is applied.)

4. Fit the remote sensor to the tabs of the back case and mount it.

TD831138-02_W-2WAY.indb 65

2007/07/26 14:32:04

Advertising