Features of w-2way eco-i system – Sanyo DHX4852 User Manual

Page 8

Advertising
background image

1-4

Outline of W-2Way ECO-i SYSTEM

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

2. Features of W-2WAY ECO-i SYSTEM

2-1. Outline of W-2WAY ECO-i SYSTEM

System example

ADDITION

CONCENTRATION

If indoor/outdoor units need servicing, a ball
valve (field supply) cuts off non-operational
units to let other units stay running.

* The capacity after the setting

must not exceed 32 PS.

Since all tubings are

concentrated into

one pipe shaft, you

can minimize piping

space and construc-

tion labor

Maximum number of combined outdoor units

Maximum horsepower of combined outdoor units

Maximum number of connectable indoor units

Indoor/outdoor unit capacity ratio

Maximum actual tubing length

Maximum level difference (when outdoor unit is lower)

Maximum total tubing length

2

32 HP

40

50~130%

492 ft

164 (131) ft

984 ft

System limitations

CONNECTION

If your indoor capacity load

changes in the future, it’s easy to

add on both indoor and outdoor

units using the same tubing.

*If additional installation of outdoor and indoor units is

expected, the sizeof refrigerant tube should be decided
according to the total capacity after the addition.

Combination of outdoor units

The DC inverter unit can be used independently or in combination.

CAUTION

R407C models and R22 models must not be used in combination with each
other.

1

1

2

10
16

10

16

20

26

32

Total horse

power

Inverter unit

Combination of outdoor units

1

2

1

TD831138-02_W-2WAY.indb 4

2007/07/26 14:30:24