Design of W-2WAY ECO-i SYSTEM Unit Specifications

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

1. Model Selecting and Capacity Calculator

Liquid tubing size

Amount of refrigerant

(in. (mm))

charge (oz/ft.)

ш1/4" (ш6.35)

0.279

ш3/8" (ш9.52)

0.602

ш1/2" (ш12.7)

1.38

ш5/8" (ш15.88)

1.99

ш3/4" (ш19.05)

2.78

ш7/8" (ш22.22)

3.93

Table 2-7 Amount of Refrigerant Charge

ш7/8"

(ш22.22)

ш3/8" (ш9.52)

ш1/4" (ш6.35)

95,500

(28.0)

153,600

(45.0)

ш1-1/8"

(ш28.58)

Flare connection

Brazing connection

ш1/2" (ш12.7)

Flare connection

(

A

B

)

Balance tubing

Liquid tubing

Gas tubing

BTU/h

(kW)

Table 2-8 Outdoor Unit Tubing Connection Size

Table 2-9 Indoor Unit Tubing Connection Size

Balance tube

Liquid tube

Gas tube

ш5/8" (ш15.88)

ш3/8" (ш9.52)

ш1/4" (ш6.35)

ш1/2" (ш12.7)

Gas tubing

Liquid tubing

Indoor unit type

7

9

12

18

24

36

48

Note: Use C1220T-1/2H material for tubing over ш3/4" (ш22.22).

Unit: in. (mm)

Unit: in. (mm)

Table 2-10 Refrigerant tubing (Existing tubing can be used.)

Tubing size (in. (mm))

Material O

Material 1/2H • H

ш1/4" (ш6.35)

t1/32" (0.8)

ш7/8" (ш22.22)

t5/128" (1.0)

ш3/8" (ш9.52)

t1/32" (0.8)

ш1" (ш25.40)

t5/128" (1.0)

ш1/2" (ш12.7)

t1/32" (0.8)

ш1-1/8" (ш28.58)

t5/128" (1.0)

ш5/8" (ш15.88)

t5/128" (1.0)

ш1-1/4" (ш31.75)

t3/64" (1.1)

ш3/4" (ш19.05)

over t5/128" (1.0)

ш1-3/8" (ш34.93)

over t3/64" (1.15)

* When bending the tubes, use a bending

radius that is at least 4 times the outer
diameter of the tubes.
In addition, take sufficient care to avoid
crushing or damaging the tubes when
bending them.

TD831138-02_W-2WAY.indb 7

2007/07/26 14:30:29