Ceiling-mounted type (t type) – Sanyo DHX4852 User Manual

Page 172

Advertising
background image

4-58

W-2WAY ECO-i SYSTEM Unit Specifications

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

6. Ceiling-Mounted Type (T Type)

Unit specifications (B)

MODEL No.

Indoor Unit

THX1852

POWER SOURCE

208 - 230 V / 1ø / 60 Hz

PERFORMANCE

Cooling

Heating

Capacity

BTU / h

19,000

21,000

kW

5.6

6.3

Air circulation (Hi / Me / Lo)

CFM

450 / 390 / 320

Moisture removal (High)

Pints / h

4.23

ELECTRICAL RATINGS

Voltage rating

V

208

230

208

230

Available voltage range

V

187 - 253

187 - 253

Running amperes

A

0.15

0.14

0.15

0.17

Power input

W

16

16

16

18

Power factor

%

51

50

51

46

Max. starting amperes

A

2

2

2

2

FEATURES

Controls

Microprocessor

Fan speeds

3 and Automatic control

Air filter

Washable, easy access, long life (2,500hr)

Refrigerant control

Electronic expansion valve

Operation sound (Hi / Me / Lo)

dB-A

36 / 33 / 30

Refrigerant tubing connections

Flare type

Refrigerant tube di-

ameter

Liquid tube

in. (mm)

1 / 4 (6.35)

Gas tube

in. (mm)

1 / 2 (12.7)

Drain connection

25 A, OD 1-1 / 32”

Remote controller

Optional (RCS-TM80BG, RCS-TRP80AAB.WL)

Refrigerant tubing kit / Accessories

Optional / –

Color (Approximate value)

Munsell 10Y 9.0 / 0.4, RAL 9010-GL

DIMENSIONS & WEIGHT

Unit dimensions

Package dimensions

Unit dimensions

Height

in. (mm)

8-9 / 32 (210)

11-1 / 32 (280)

Width

in. (mm)

35-13 / 16 (910)

38-25 / 32 (958)

Depth

in. (mm)

26-25 / 32 (680)

30-23 / 32 (780)

Net weight

lbs. (kg)

46 (21)

Shipping weight

lbs. (kg)

53 (24)

Shipping volume

ft

3

(m

3

)

7.6 (0.215)

Rated conditions

Colling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB
Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB

TD831138-02_W-2WAY.indb 58

2007/07/26 14:33:04

Advertising