W-2WAY ECO-i SYSTEM Unit Specifications

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

2. 4-Way Air Discharge Semi-concealed Type (X Type)

2-2. Major Component Specifications
Indoor unit (A)

MODEL No.

XHX1252

Power source

208 - 230 V / 1ø / 60 Hz

Controller P.C.B. Ass'y

CR-SXRP56B-B (Microprocessor)

Fan...(Number diameter / length in. (mm))

Turbo (1...ш18-7/64 (ш460))

Fan motor

Model...Nominal output

W

DK8-53B280HB...50W

Power source

280 VDC

No. of pole...r.p.m. (230V, High)

rpm

8P...360

Coil resistance
(Ambient temperature 68°F)

RED – WHT : 87.0
WHT – BLU : 87.0
BLU – RED : 87.0

Run capacitor

VAC, µF

Safety device

fuse

Operating temperature

Open °F (°C)

285

+4
–5

(141

+2
–3

)

Electronic expansion valve

Coil

UKV-U030E

Coil resistance (at 68°F)

ORG – GRY : 46

YEL – GRY : 46

RED – GRY : 46

BLK – GRY : 46

Valve body

UKV-18D31

Heat exchanger

Coil

Aluminum plate fin / Copper tube

Rows...fin pitch

in. (mm)

2...3/64 (1.25)

Face area

ft

2

(m

2

)

3.88 (0.360)

Panel

Model No.

PNR-XH3652

Auto louver motor

MP24ZN

Coil resistance (at 77°F)

380

Ω ± 7% / phase

Drain pump

PLD-12230ST

Rated

V, Hz, W

AC230V, 60Hz, 10.8W

Total head & capacity

in. (mm), gal/
min (cc/min)

25-3/16 (640), 0.11 (400)