Outdoor unit – Sanyo DHX4852 User Manual

Page 117

Advertising
background image

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

4-3

W-2WAY ECO-i SYSTEM Unit Specifications

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

1. Outdoor Unit

Unit Specifications (2)

MODEL NAME

W-2WAY ECO-i Capacity Control Outdoor Unit <16 horsepower>

MODEL No.

CHDX14053

POWER SOURCE

208-230V/3ø/60Hz

PERFORMANCE

Cooling capacity

BTU / h (kW)

153,600 (45.0)

Heating capacity

BTU / h (kW)

170,600 (50.0)

UNIT DIMENSIONS

Height

in. (mm)

74-9/32 (1887)

Width

in. (mm)

35-1/32 (890)

Depth

in. (mm)

Ceiling dimension : 35-1/32 ~ +2-3/8

(890 ~ +60)

Net weight

lbs. (kg)

760 (345)

Color (Munsell code)

Silky shade (1Y 8.5 / 0.5)

ELECTRICAL RATINGS

Voltage rating

V

208

230

Cooling

Running amperes

A

46.6

44.8

Power input

kW

13.3

13.3

Power factor

%

79

75

Heating

Running amperes

A

52.4

49.2

Power input

kW

13.2

13.2

Power factor

%

70

67

Starting amperes

A

172

162

COMPRESSOR

Type - Q'ty

Hermetic type x 3

Motor output

kW

3 + 4.5 x 2

Refrigeration oil

Type

FV68S (Ether oil)

Charge amount

gal

1.56

Crankcase heater

W

25 + 32 x 2

Capacity control

%

Refrigerant amount at shipment

lbs. (kg)

R410A - 28.7 (13.0)

Refrigerant control

Electronic expansion valve

Defrost method

Reverse-cycle defrost, outdoor unit cycle defrost

Heat exchanger

Aluminum plate fin / Copper tube

FAN DEVICE

Type - Q'ty

Propeller fan x 1

Air circulation

CFM

7,770

External static pressure

in.WG

0

Motor output (No. of poles)

kW

0.7/8P

Protective devices

High pressure switch, overcurrent (CT method)

TUBING

Refrigerant tubing

Gas tube

in. (mm)

ш1-1/8 (ш28.58) (Brazing)

Liquid tube

in. (mm)

ш1/2 (ш12.7) (Flare nut)

Balance tube

in. (mm)

ш1/4 (ш6.35) (Flare nut)

Drain port

External air temperature operation range

°F

Cooling: 14 ~ 109 °F (DB)

Heating: -4 ~ 59 (WB)

Operation sound (Hi)

dB-A

62.0 (Quiet mode: 59.0)

Primary accessories

Connection tubing

ш1-1/8 (ш28.58)

* Performance, electrical characteristics values and operating sound are based on JIS B8616 package A/C.
(Colling : Indoor intake air temperature 80°F DB / 67°F WB. Outdoor intake air temperature 95°F DB.)
(Heating : Indoor intake air temperature 70°F DB. Outdoor intake air temperature 47°F DB / 43°F WB.)

TD831138-02_W-2WAY.indb 3