Wireless remote controller – Sanyo DHX4852 User Manual

Page 62

Advertising
background image

3-14

Control of W-2WAY ECO-i SYSTEM

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

2. Wireless Remote Controller

CN1

1 2

1 2

1

2

(main)

(sub)

Indoor

unit

Control unit

Remote controller
terminal board

Ground

Remote control wiring (field supply)

(optional)

(optional)

Wireless receiver unit

Wired remote controller

When 1 indoor unit is operated with 2 remote controllers:
(The indoor unit runs according to which of the remote controllers is assigned as the main or sub unit.)

* Use field wiring cables with a

cross-sectional area of at least
AWG#20 to AWG#14.

* The maximum total length of

crossover cables must be no
longer than 1320 ft.

*

*

CN1

(optional)

1

2

2

1

2

1

2

1 2

1 2

(optional)

1

Indoor

unit No. 1

Receiver

unit

Ground

Remote controller

terminal board

Indoor

unit No. 2

Indoor

unit No. 3

Indoor

unit No. 4

(main)

(sub)

Remote control
wiring among the
control groups
(field supply)

Wired remote

controller

When several groups of indoor units are operated with 2 remote controllers:
(The remote controller (main or sub unit) can operate with any indoor unit.)

* Use field wiring cables with a

cross-sectional area of at least
AWG#20 to AWG#14.

* The maximum total length of

crossover cables must be no
longer than 660 ft.

*

*

Wireless receiver

unit

Ground

Ground

Ground

Fig. 3-11

Fig. 3-12

S003

Bit 1: OFF ON

2-10. How to Use the Test Run Setting

1. Set DIP switch [S003] No. 1 on the wireless receiver unit

PCB from OFF to ON.

2. All indicator lamps in the display section blink during test

run operation.

3. No temperature control is available during the test run.
4. After the test run, be sure to reset DIP switch No. 1 back

to the OFF position and check that no indicator lamps
are blinking. Then remount and attach the PCB cover as
before.

To avoid placing excessive operating load on the equip-

ment, use this function only when conducting the test run.

The unit does not receive remote controller signals for ap-

proximately 1 minute after the power is turned ON. This is
not a malfunction. (The signals are received, but have no
immediate effect.)

NOTE