Design of W-2WAY ECO-i SYSTEM Unit Specifications

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

<Heating>

Outdoor unit corrected heating capacity (5) =

Outdoor unit rated heating capacity × Correction coefficient for model ((1)
Page

2-12) × Correction coefficient for outdoor temperature conditions ((2)

Page

2-12) × Correction coefficient for tubing length and elevation difference

((3) Page

2-13) × Correction coefficient for frosting/defrosting ((4) Page 2-12)

* However, if the outdoor unit corrected heating capacity [5] is greater than 100%, then the outdoor unit corrected heating

capacity is considered to be 100%.

Corrected heating capacity of each indoor unit (5) = Rated heating capacity for that indoor unit × Correction coefficient for

indoor temperature conditions at that indoor unit ((2) Page

2-13) × Distribution ratio based on tubing length and elevation

difference at that indoor unit.

However, the corrected heating capacity of each indoor unit is found as shown below.
If (2) < 100% and (2)

×

(3) > 100%: Corrected heating capacity for that indoor unit (5) = Rated heating capacity for that indoor unit

If (2)

≥ 100%: Corrected heating capacity for that indoor unit (5) = Rated heating capacity for that indoor unit

×

(2)

* Characteristic graphs are shown on the pages listed above next to each correction item. Find each correction coefficient

from the appropriate conditions.

4. Calculating the actual indoor unit capacity based on the indoor/outdoor corrected capacity ratio

Calculate the actual capacity of each indoor unit from the values (found in (3)) for the corrected outdoor unit capacity and the
corrected capacity of each indoor unit.

<Cooling capacity>

Corrected indoor/outdoor capacity ratio during cooling (Ruc) = Total corrected cooling capacity of all indoor units in that system /
Corrected outdoor unit cooling capacity

If the corrected outdoor unit cooling capacity is greater than or equal to the total corrected unit cooling capacity of all indoor units
in that system (Ruc 1), then:

Actual cooling capacity of each indoor unit (7) = Corrected cooling capacity of each indoor unit (5) (In other words, the cor-
rection coefficient (6), based on the corrected indoor/outdoor capacity ratios for each indoor unit, is 1.)

If the corrected outdoor unit cooling capacity is less than the total corrected unit cooling capacity of all indoor units in that sys-
tem (Ruc > 1), then:

(Actual cooling capacity of each indoor unit (7)) = (Corrected cooling capacity of each indoor unit (5)) Ч (0.25 Ч Ruc + 0.75)
/ Ruc
(In other words, the correction coefficient (6), based on the corrected indoor/outdoor capacity ratios for each indoor unit, is
the underlined part in the formula above.)

<Heating capacity>

Corrected indoor/outdoor capacity ratio during heating (Ruh) = Total corrected heating capacity of all indoor units in that system
/ Corrected outdoor unit heating capacity

If the corrected outdoor unit heating capacity is greater than or equal to the total corrected unit heating capacity of all indoor
units in that system (Ruh 1), then:

Actual heating capacity of each indoor unit (7) = Corrected heating capacity of each indoor unit (5)

(In other words, the correction coefficient (6), based on the corrected indoor/outdoor capacity ratios for each indoor unit, is 1.)

If the corrected outdoor unit heating capacity is less than the total corrected unit heating capacity of all indoor units in that sys-
tem (Ruh > 1), then:

(Actual heating capacity of each indoor unit (7)) = (Corrected heating capacity of each indoor unit (5)) Ч (0.1 Ч Ruh + 0.9) /
Ruh
(In other words, the correction coefficient (6), based on the corrected indoor/outdoor capacity ratios for each indoor unit, is
the underlined part in the formula above.)

1. Model Selecting and Capacity Calculator

TD831138-02_W-2WAY.indb 11

2007/07/26 14:30:31