5. TEST RUN

Possible cause of malfunction

Alarm

Message

Activation of

protective

device

Protective device in outdoor unit

is activated.

Compressor therminal protector is activated.

Power supply voltage is unusual. (The voltage is more than 260 V or less

than 160 V between L1 and L2 phase.)

P02

Incorrect discharge temperature. (Comp. No. 1)

P03

High pressure switch is activated.

P04

Negtive (defective) phase.

P05

Compressor running failure resulting from missing phase in the

compressor wiring, etc. (Start failure not caused by IPM or no gas.)

P16

Incorrect discharge temperature. (Comp. No. 2)

P17

Compressor 3 discharge temp. failure

P18

Outdoor unit fan motor is unusual.

P22

Overcurrent at time of compressor runs more than 80Hz (DCCT

secondary current or ACCT primary current is detected at a time other

than when IPM has tripped.)

P26

IPM trip (IPM current or temperature)

H31

Inverter for compressor is unusual. (DC compressor does not operate.)

P29

Thermistor fault

Indoor thermistor is either open

or damaged.

Indoor coil temp. sensor (E1)

<<F01>>

Indoor coil temp. sensor (E2)

<<F02>>

Indoor coil temp. sensor (E3)

<<F03>>

Indoor suction air (room) temp. sensor (TA)

<<F10>>

Indoor discharge air temp. sensor (BL)

<<F11>>

Outdoor thermistor is either

open or damaged.

Comp. No. 1 discharge gas temp. sensor (DISCH1)

F04

Comp. No. 2 discharge gas temp. sensor (DISCH2)

F05

Outdoor No. 1 coil gas temp. sensor (EXG1)

F06

Outdoor No. 1 coil liquid temp. sensor (EXL1)

F07

Outdoor air temp. sensor (AIR TEMP)

F08

Compressor intake port temperature sensor (RDT)

F12

High pressure sensor. Negative (defective) N phase.

F16

Low-pressure sensor failure

F17

Compressor 3 discharge temp. sensor failure (DISCH3)

F22

Outdoor No. 2 coil gas temp. sensor (EXG2)

F23

Outdoor No. 2 coil liquid temp. sensor (EXL2)

F24

EEP ROM on indoor unit PCB failure

F29

Protective

device for

compressor is

activated

Protective device for

compressor No.1 is activated.

EEP ROM on the main or sub outdoor unit PCB has failed.

F31

Current is not detected when comp. No. 1 is ON.

H03

Discharge gas temperature of the comp. No. 1 is not detected.

Temp. sensor is not seated at the sensor holder.

H05

Protective device for

compressor No.2 is activated

Overload current is detected.

H11

Lock current is detected.

H12

Current is not detected when comp. No.2 is ON.

H13

Discharge gas temperture of comp. No.2 is not detected.

H15

Protective device for

compressor No.3 is activated.

Compressor No.3 current trouble (overcurrent)

H21

Compressor No.3 current trouble (locked)

H22

Compressor No.3 CT sensor disconnected or short circuit

H23

Compressor No.3 discharge temp. sensor disconnected

H25

Low pressure switch is activated.

H06

Low oil level.

H07

Oil sensor fault.

(Disconnection, etc.)

Comp. No.1 oil sensor

H08

Comp. No.2 oil sensor

H27

Oil sensor (connection) failure

H28

Continued

TD831138-02_W-2WAY.indb 15

2007/07/26 14:33:24