5. TEST RUN

Case 3B

Automatic Address Setting in Cooling Mode

Indoor and outdoor unit power cannot be turned ON for each system separately. In the following, automatic setting of indoor
unit addresses is not possible if the compressors are not operating. Therefore perform this process only after completing all
refrigerant tubing work.
Automatic address setting can be performed during Cooling operation.

Automatic Address Setting from Outdoor Unit

1. Perform steps 1 - 4 in the same way as for Case 2 .

5. Turn the indoor and outdoor unit power ON at all systems.

6. To perform automatic address setting in Cooling mode , on the outdoor main unit control PCB in the refrigerant system

where you wish to set the addresses, short-circuit the mode change 2P pin (CN101). At the same time, short-circuit the
automatic address pin (CN100) for 1 second or longer, then release it. (Be sure to perform this process for one system at a
time. Automatic address settings cannot be performed for more than one system at the same time.)

(Communication for automatic address setting begins,

the compressors turn ON, and automatic address setting in

Cooling mode begins.)
(All indoor units operate.)

* To cancel, again short-circuit the automatic address pin (CN100) for 1 second or longer, then release it. The

LED that indicates automatic address setting is in progress turns OFF and the process is stopped. Be sure to
perform automatic address setting again.

(Automatic address setting is completed when the compressors stop and LEDs 1 and 2 on the outdoor main unit control
PCB turn OFF.)

7. At the outdoor main unit in the next (different) system, short-circuit the automatic address pin (CN100) for 1 second or

longer, then release it.

(Repeat the same steps to complete automatic address setting for all units.)

8. Operation from the remote controllers is now possible.

* Automatic address setting in Cooling mode cannot be done from the remote controller.

Automatic Address Setting* from the Remote Controller

Selecting each refrigerant system individually for automatic address setting
---Automatic address setting for each system: Item code “A1.”

1. Press the remote controller timer time

button and

button at the same

time.
(Press and hold for 4 seconds or longer.)

2. Next, press either the temperature setting

or

button. (Check that

the item code is “A1.”)

3. Use either the

or

button to set the system No. to perform auto-

matic address setting.

4. Then press the

button.

(Automatic address setting for one refrigerant system begins.)

(When automatic address setting for one system is completed, the system returns
to normal stopped status.) <Approximately 4 - 5 minutes is required.>

(During automatic address setting, “NOW SETTING” is displayed on the remote
controller. This message disappears when automatic address setting is completed.)

5. Repeat the same steps to perform automatic address setting for each successive system.