Sanyo DHX4852 User Manual

Page 94

Advertising
background image

3-46

Control of W-2WAY ECO-i SYSTEM

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

4. System Controller

How to connect electrical wiring

(1) Connect B1, B2 to indoor PCB T10 connector using
the accessory 6P connector. (with fuse) (*No polarity)
Total wire length is less than 985 ft. and size is
AWG#18.

(2) Connect B5, B6 to indoor unit 2P terminal base.
(*No polarity). Wire size is AWG#18.

Basic wiring

Terminals for remote monitoring

Basic wiring diagram of control wiring

A max. of 64 indoor units and 30 outdoor units can be
connected in 1 system.

Up to 10 system controllers can be connected in 1
system.

B1

Indoor unit PCB

T10
(YEL)

2P terminal base

Indoor unit

System controller

Accessory connctor

Wire joint connection

B2

B3

B4

B5

B6

U1

U2

A1

<Back side of system controller>

A2

A3

A4

A5

A6

B6

B5

B4

B3

B2

B1

Inter-unit

control wiring

System controller

RC1

1-1

RC2

RC3

2-1

3-1

B1:

B2:

B3:

B4:

B5:

B6:

Power supply: DC12V *No polarity
To T10 connector on indoor PCB

Inter-unit control wiring. (Low voltage)
To indoor unit 2P terminal base (U1, U2)
*No polarity

Auxiliary of inter-unit control wiring

Not be used

A1:

A2:

A3:

Common input for turning air conditioners on or off.

A4:

A5:

A6:

ON operation state indicator output.

Alarm indicator output.

Common indicator output.

Input for turning off air conditioners concurrently.

Input for turning on air conditioners concurrently.

Fig. 3-27

Fig. 3-28

Electrical wiring

TD831138-02_W-2WAY.indb 46

2007/07/26 14:31:47

Advertising