W-2WAY ECO-i SYSTEM Unit Specifications

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

6. Ceiling-Mounted Type (T Type)

Indoor unit (C)

MODEL No.

THX2452

Power source

208 - 230 V / 1ø / 60 Hz

Controller P.C.B. Ass'y

CR-SXRP56B-B (Microprocessor)

Fan...(Number diameter / length in. (mm))

Centrifugal (3 ... ш5-1/2 (ш140))

Fan motor

Model...Nominal output

W

DK8-63D280HB...60W

Power source

340 VDC

No. of pole...r.p.m. (230V, High)

rpm

8P...980

Coil resistance
(Ambient temperature 68°F)

RED – WHT : 53.0
WHT – BLU : 53.0
BLU – RED : 53.0

Run capacitor

VAC, µF

Safety device

fuse

Operating temperature

Open °F (°C)

285

+4
–5

(141

+2
–3

)

Electronic expansion valve

Coil

UKV-U030E

Coil resistance (at 68°F)

ORG – GRY : 46

YEL – GRY : 46

RED – GRY : 46

BLK – GRY : 46

Valve body

UKV-25D32

Heat exchanger

Coil

Aluminum plate fin / Copper tube

Rows...fin pitch

in. (mm)

3...7/128 (1.4)

Face area

ft

2

(m

2

)

2.39 (0.222)

TD831138-02_W-2WAY.indb 62