Design of W-2WAY ECO-i SYSTEM Unit Specifications

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

1. Model Selecting and Capacity Calculator

Table 2-2 Refrigerant Charge Amount at Shipment (for outdoor unit)

DC

CHDX09053

CHDX14053

(oz)

423

458

Table 2-4 System Limitations

Max. No. allowable connected outdoor units

2

*1

Max. capacity allowable connected outdoor units

307,100 BTU/h (32 hp, 90 kW)

Max. connectable indoor units

40

Max. allowable indoor/outdoor capacity ratio

50 – 130 %

*1: Up to 2 units can be connected if the system has been extended.

Additional refrigerant charge amount is calculated from the liquid tubing total length as follows.

Table 2-3 Amount of Refrigerant Charge Per Meter, According to Liquid Tubing Size

Liquid tubing size

Amount of refrigerant

(in. (mm))

charge (oz/ft.)

ш1/4" (ш6.35)

0.279

ш3/8" (ш9.52)

0.602

ш1/2" (ш12.7)

1.38

ш5/8" (ш15.88)

1.99

ш3/4" (ш19.05)

2.78

ш7/8" (ш22.22)

3.93

Required amount of charge = (Amount of refrigerant charge per
meter of each size of liquid tube × its tube length) + (...) + (...)

* Always charge accurately using a scale for weighing.

* If the existing tubing is used, and the amount of on-site additional

refrigerant charge exceeds the value listed below, then change the
size of the tubing to reduce the amount of refrigerant.

Max. additional charge for 1 outdoor unit : 62 lbs
Max. additional charge for 2 outdoor units : 111 lbs