Design of W-2WAY ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1. Model Selecting and Capacity Calculator
Table 2-2 Refrigerant Charge Amount at Shipment (for outdoor unit)
DC
CHDX09053
CHDX14053
(oz)
423
458
Table 2-4 System Limitations
Max. No. allowable connected outdoor units
2
*1
Max. capacity allowable connected outdoor units
307,100 BTU/h (32 hp, 90 kW)
Max. connectable indoor units
40
Max. allowable indoor/outdoor capacity ratio
50 – 130 %
*1: Up to 2 units can be connected if the system has been extended.
Additional refrigerant charge amount is calculated from the liquid tubing total length as follows.
Table 2-3 Amount of Refrigerant Charge Per Meter, According to Liquid Tubing Size
Liquid tubing size
Amount of refrigerant
(in. (mm))
charge (oz/ft.)
ш1/4" (ш6.35)
0.279
ш3/8" (ш9.52)
0.602
ш1/2" (ш12.7)
1.38
ш5/8" (ш15.88)
1.99
ш3/4" (ш19.05)
2.78
ш7/8" (ш22.22)
3.93
Required amount of charge = (Amount of refrigerant charge per
meter of each size of liquid tube × its tube length) + (...) + (...)
* Always charge accurately using a scale for weighing.
* If the existing tubing is used, and the amount of on-site additional
refrigerant charge exceeds the value listed below, then change the
size of the tubing to reduce the amount of refrigerant.
Max. additional charge for 1 outdoor unit : 62 lbs
Max. additional charge for 2 outdoor units : 111 lbs