System design – Sanyo DHX4852 User Manual

Page 32

Advertising
background image

2-22

Design of W-2WAY ECO-i SYSTEM Unit Specifications

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

15 to 30

°

B

A

B

A

Arrow view

Horizontal

line

View as seen

from arrow

Ball valve

(BV: purchased

separately)

Main tubing

Types of vertical trap specifications

(If only 1 unit is connected, a ball

valve is also needed on this side.)

Indoor unit (1)

(When not using ball valve)

(When using ball valve)

Branch tubing is

directed upward.

(Each unit is
connected to tubing
that is either level or
is directed
downward.)

Main tubing

Indoor unit

More than

8 in

Indoor unit (more than 2 units)

Horizontal

Indoor unit is directed downward

Installing distribution joint

(1) Refer to “HOW TO ATTACH DISTRIBUTION JOINT”

enclosed with the optional distribution joint kit (APR-
CHP680BA, CHP1350BA, P160BA, P680BA,
P1350BA).

(2) In order to prevent accumulation of refrigerant oil in

stopped units, if the main tubing is horizontal then
each branch tubing length should be at an angle that
is greater than horizontal. If the main tubing is vertical,
provide a raised starting portion for each branch.

(3) If there are height differences between indoor units

or if branch tubing that follows a distribution joint is
connected to only 1 unit, a trap or ball valve must be
added to that distribution joint. (When adding the ball
valve, locate it within 1.3 ft of the distribution joint.)

(Consult with SANYO separately concerning the ball
valve.)

If a trap or ball valve is not added, do not operate
the system before repairs to a malfunctioning
unit are completed. (The refrigerant oil sent
through the tubing to the malfunctioning unit will
accumulate and may damage the compressor.)

Tube branching methods (horizontal use)

2. System Design

TD831138-02_W-2WAY.indb 22

2007/07/26 14:30:44