Control of W-2WAY ECO-i SYSTEM

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

2. Wireless Remote Controller

2-15. Important Information for Installation of 2

Separate Receiver Units

When using 2 receiver units to operate 1 or more indoor units
at the same time, follow the procedure below to install them.

Installation method

1. If 2 remote controllers are installed, set one of them as

the “main remote controller” (setting at time of factory
shipment).

2. At the other remote controller, remove the receiver name-

plate and switch the DIP switch to “sub remote controller.”
Under these conditions, the receiver unit functions as the
sub receiver unit.
* The TIMER lamp lights only at the remote controller

that receives the signal.

Basic wiring diagram

* When connecting the wires, be careful not to wire

incorrectly.
(Incorrect wiring will damage the unit.)

Using 2 separate receiver units to control 1 indoor unit:

Separate

receiver unit

(main)

Separate

receiver unit

(sub)

(optional)

Remote controller

terminal board

Wire of the receiver unit (field supply)

Indoor

unit

1 2

1 2

2

1

Ground

1 2

1 2

1 2

1 2

1 2

1 2

Indoor

unit No. 1

Indoor

unit No. 2

Indoor

unit No. 3

Indoor

unit No. 8

Remote controller

terminal board

Separate

receiver unit

(main)

(optional)

Separate

receiver unit

(sub)

(optional)

Crossover cables of the
receiver unit for the
control groups (field supply)

Ground

Ground

Ground

Ground

Using 2 separate receiver units to control a group of multi-

ple indoor units:
* The main and sub receiver units will operate regard-

less of the indoor unit in which they are installed.

* Use wires that are AWG#20 to AWG#14 in diameter.
* The wiring length must not exceed 1320 ft.

* Use field wiring cables with a cross-sectional

area of at least AWG#20 to AWG#14.

* The maximum total length of crossover cables

must be no longer than 1320 ft.