Outdoor unit control pcb – Sanyo DHX4852 User Manual

Page 235

Advertising
background image

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

7-5

PCB and Functions

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

1. Outdoor Unit Control PCB

Table 7-1. Setting the System Address [S002: Rotary switch (black), S003: 2P DIP (blue)]

Outdoor system address

S002 setting

S003 setting

1P (10s digit)

2P (20s digit)

1 refrigerant

system only

1

0

OFF

OFF

Link wiring

1
2
3
4
5
6
7
8
9

1
2
3
4
5
6
7
8
9

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF

10
11
12
13
14
15
16
17
18
19

0
1
2
3
4
5
6
7
8
9

ON
ON
ON
ON
ON
ON
ON
ON
ON
ON

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF

20
21
22
23
24
25
26
27
28
29

0
1
2
3
4
5
6
7
8
9

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF

ON
ON
ON
ON
ON
ON
ON
ON
ON
ON

30

0

ON

ON

Table 7-2. Setting the Number of Indoor Units

[S004: Rotary switch (red), S005: 2P DIP (blue)]

Number of

Indoor Units

S004 Setting

S005 Setting

1

2

3

1

1

OFF

OFF

OFF

2

2

OFF

OFF

OFF

3

3

OFF

OFF

OFF

9

9

OFF

OFF

OFF

10

0

ON

OFF

OFF

11

1

ON

OFF

OFF

19

9

ON

OFF

OFF

20

0

OFF

ON

OFF

21

1

OFF

ON

OFF

29

9

OFF

ON

OFF

30

0

OFF

OFF

ON

31

1

OFF

OFF

ON

39

9

OFF

OFF

ON

40

0

ON

ON

ON

Table 7-3. Setting the Number of Outdoor Units

[S006: DIP switch (blue)]

Number of

Indoor Units

S006 Setting

1

2

3

1

ON

OFF

OFF

2

OFF

ON

OFF

3

ON

ON

OFF

4

OFF

OFF

ON

Table 7-4. Setting the Outdoor Unit address

Outdoor Unit

Address

S007 Setting

1

2

3

1

ON

OFF

OFF

2

OFF

ON

OFF

3

ON

ON

OFF

4

OFF

OFF

ON

TD831138-02_W-2WAY.indb 5

2007/07/26 14:34:03