2-34

Design of W-2WAY ECO-i SYSTEM Unit Specifications

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

4. Installation Instructions

4-9. Transporting the Outdoor Unit

When transporting the unit, have it delivered as close to the
installation site as possible without unpacking.
Use a hook for suspending the unit. (Fig. 2-17)

(Positions where anchor bolts are fastened)

31-7/64 (Installation hole pitch)

37-13/32 (Maximum dimensions)

35-3/64 (Ceiling panel dimensions)

36-7/32 (Installation hole pitch)

35-3/64 (Ceiling panel dimensions)

Installation anchor hole (4 – 19/32

× 25/32 oval holes)

When hoisting the outdoor unit, pass ropes or straps under the bottom plate

as shown in the figure at right. When hoisting, the angle between the rope
and top panel must be 70° or greater so that the rope does not come into
contact with the fan guard.
(Use 2 lengths of rope 25 ft. long or longer.)

When passing the ropes through the square holes of the bottom plate:

Place the rope in the outer edge of the square holes.

Use protective panels or padding at all locations where the rope contacts the

outer casing or other parts to prevent scratching. In particular, use protective
material (such as cloth or cardboard) to prevent the edges of the top panel
from being scratched.

Be careful of the fan.

There is danger of injury if the fan starts to turn during inspection. Be sure to
turn OFF the remote power switch before beginning inspection.

4-10. Installing the Outdoor Unit

(1) Use anchor bolts (M12 or 15/32") or similar to securely anchor the unit in

place. (Fig. 2-18)

(2) Be sure the rubber vibration insulator and platform extend to the inside of

the legs. In addition, the washers used to anchor the unit from the top must
be larger than the installation anchor holes. (Figs. 2-18 and 2-19)

Fig. 2-17

Fig. 2-18

Fig. 2-19

(3-15/16)

(3-15/16)

3-29/64

25/32

1-31/32

Washer

Plate leg

Base

Anchor bolts

Vibration insulator

WARNING

CAUTION

1-33/64

19/32

1-31/32

4 – 19/32 25/32 hole

(Detailed view of legs)

Surf

ace where

installation anchor bra

ck

ets are

installed

Unit: in.

Unit: in.

74-1/64 (Ceiling panel dimensions)

70-5/64 (Installation hole pitch)

35-3/64 (Ceiling panel dimensions)

35-3/64 (Ceiling panel dimensions)

35-3/64 (Ceiling panel dimensions)

31-7/64 (Installation hole pitch)

31-7/64 (Installation hole pitch)

36-7/32 (Installation hole pitch)

37-13/32 (Maximum dimensions)

The vibration insulator, base, or platform must
be large enough to bear the full surface of the
base plate legs.

Unit: in.

Top view

TD831138-02_W-2WAY.indb 34

2007/07/26 14:31:06

Advertising