1-6. Calculation of Actual Capacity of Indoor Unit

Calculating the actual capacity of each indoor unit

Because the capacity of a multi air-conditioner changes according to the temperature conditions, tubing length, elevation dif-
ference and other factors, select the correct model after taking into account the various correction values. When selecting The
model, calculate the corrected capacities of the outdoor unit and each indoor unit. Use the corrected outdoor unit capacity and
the total corrected capacity of all the indoor units to calculate the actual final capacity of each indoor unit.

1. Outdoor unit capacity correction coefficient

Find the outdoor unit capacity correction coefficient for the following items.

(1) Capacity correction for the outdoor unit model

The capacity correction coefficient is 1.00.

(2) Capacity correction for the outdoor unit temperature conditions

From the graph of capacity characteristics on page

2-12, use the outdoor temperature to find the capacity correction coef-

ficient.

(3) Capacity correction for the outdoor unit tubing length and elevation difference

From the graph of capacity change characteristics on page

2-13, use the tubing length and elevation difference to find the

capacity correction coefficient.
The outdoor unit correction coefficient is the value which corresponds to the most demanding indoor unit.

(4) Capacity correction for outdoor unit frosting/defrosting during heating

From the table on page

2-12, find the capacity correction coefficient.

2. Indoor unit capacity correction coefficients

Find the indoor unit capacity correction coefficient for the following items.

(2) Capacity correction for the indoor unit temperature conditions

From the graph of capacity characteristics on page

2-13, use the indoor temperature to find the capacity correction coeffi-

cient.

(3) Capacity distribution ratio based on the indoor unit tubing length and elevation difference

First, in the same way as for the outdoor unit, use the tubing length and elevation difference for each indoor unit to find the
correction coefficient from the graph of capacity change characteristics on page

2-13. Then divide the result by the outdoor

unit correction coefficient to find the capacity distribution ratio for each indoor unit.

However, the corrected cooling capacity of each indoor unit is found as shown below.
If (2) < 100% and (2)

×

(3) > 100%: Corrected cooling capacity for that indoor unit [5] = Rated cooling capacity for that indoor unit

If (2)

≥ 100%: Corrected cooling capacity for that indoor unit (5) = Rated cooling capacity for that indoor unit

×

(2)

Capacity distribution ratio for each indoor unit (3) = Correction coefficient for that indoor unit / Correction coefficient for the outdoor uni

t

3. Calculating the corrected capacities for the outdoor unit and each indoor unit

The corrected capacities for the outdoor unit and each indoor unit are calculated form the formula below.

<Cooling>

Outdoor unit corrected cooling capacity (5) =

Outdoor unit rated cooling capacity × Correction coefficient for model ((1)
Page

2-12) × Correction coefficient for outdoor temperature conditions ((2)

Page

2-12) × Correction coefficient for tubing length and elevation difference

((3) Page

2-13)

* However, if the outdoor unit corrected cooling capacity [5] is greater than 100%, then the outdoor unit corrected cooling

capacity [5] is considered to be 100%.

Corrected cooling capacity of each indoor unit (5) = Rated cooling capacity for that indoor unit × Correction coefficient for

indoor temperature conditions at that indoor unit ((2) Page

2-13) × Distribution ratio based on tubing length and elevation dif-

ference at that indoor unit ((3) Page

2-13)

However, the corrected cooling capacity of each indoor unit is found as shown below.
If (2) < 100% and (2)

×

(3) > 100%: Corrected cooling capacity for that indoor unit [5] = Rated cooling capacity for that indoor unit

If (2)

≥ 100%: Corrected cooling capacity for that indoor unit (5) = Rated cooling capacity for that indoor unit

×

(2)

Capacity distribution ratio for each indoor unit (3) = Correction coefficient for that indoor unit / Correction coefficient for the outdoor uni

t

1. Model Selecting and Capacity Calculator