Model selecting and capacity calculator – Sanyo DHX4852 User Manual

Page 23

Advertising
background image

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

2-13

Design of W-2WAY ECO-i SYSTEM Unit Specifications

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

Graph of indoor unit capacity characteristics (2 – (2))

Rate of cooling capacity change (%)

Indoor unit cooling capacity characteristics

Indoor unit heating capacity characteristics

indicates the rating point.

indicates the rating point.

Indoor air intake temp. (°F WB)

Rate of heating capacity change (%)

Indoor air intake temp. (°F DB)

120

110

100

90

80

110

105

100

95

90

57 59 60 62 64 66 68 69 71 73 75 77

59 60 62 64 66 68 69 71 73 75 77 78 80

Graph of capacity change characteristics resulting from tubing length and elevation difference (1 / 2 – (3))

<Cooling>

Ele

vation diff

erence (ft)

Base capacity

change rate

Ele

vation diff

erence (ft)

*1

92 90 88 86 84 82 80 78 76

94

96

98

100

%

0

98

66

33

131 164 197 230 262 295 328 361 394 427 459 492

164

131

98

66

33

0

-33

-66

-98

-131

Equiv

0

98

66

33

131 164 197 230 262 295 328 361 394 427 459 492

alent length (ft)

Equivalent length (ft)

<Heating>

Base capacity

change rate

164

131

98

66

33

0

-33

-66

-98

-131

The positive side for the elevation difference indicates that the outdoor unit is installed at a higher position than the indoor units.
The negative side indicates the opposite.

The capacity loss that is caused by the tubing length can be reduced by increasing the sizes of the discharge tubes and suc-

tion tubes. Refer to Table 2-13 and make the appropriate changes. However be sure that the total length does not exceed the
maximum.
* The only sizes which can be increased are the LM (main tube with the largest diameter) gas tubes, and the changes are

limited to those shown in Table 2-13.
In addition, note that the additional refrigerant charge is determined only by the narrow-tube size.

Table 2-13 Equivalent Length Correction Coefficient when the Size of the Discharge Tubes and Suction Tubes (LM)

is Increased

Standard tubing diameter
(gas tube, in.(mm))

ш1/2"

ш5/8"

ш3/4"

ш7/8"

ш1-1/8"

(ш12.7)

(ш15.88)

(ш19.05)

(ш22.22)

(ш28.58)

Tubing diameter after change
(gas tube,in.(mm))

ш5/8"

ш3/4"

ш7/8"

ш1-1/8"

ш1-3/8"

(ш15.88)

(ш19.05)

(ш22.22)

(ш28.58)

(ш34.93)

Equivalent length correction
coefficient

0.4

0.5

0.6

*

If the size of the discharge tubes and suction tubes (LM) have been increased, apply the correction coefficient from Table
2-13 and calculate the equivalent length of the LM section.

Equivalent length of tubing after size increase
= Standard tubing equivalent length × Equivalent length correction coefficient

1. Model Selecting and Capacity Calculator

TD831138-02_W-2WAY.indb 13

2007/07/26 14:30:33