Wall-mounted type (k type) – Sanyo DHX4852 User Manual

Page 180

Advertising
background image

4-66

W-2WAY ECO-i SYSTEM Unit Specifications

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

7. Wall-Mounted Type (K Type)

7-1. Specifications

Unit specifications (A)

MODEL No.

Indoor Unit

KHX0752

POWER SOURCE

208 - 230 V / 1ø / 60 Hz

PERFORMANCE

Cooling

Heating

Capacity

BTU / h

7,500

8,500

kW

2.2

2.5

Air circulation (Hi / Me / Lo)

CFM

350 / 280 / 210

Moisture removal (High)

Pints / h

3.38

ELECTRICAL RATINGS

Voltage rating

V

208

230

208

230

Available voltage range

V

187 - 253

187 - 253

Running amperes

A

0.25

0.26

0.25

0.26

Power input

W

50

56

50

56

Power factor

%

96

94

96

94

Max. starting amperes

A

1

1

1

1

FEATURES

Controls

Microprocessor

Fan speeds

3 and Automatic control

Air filter

Washable, easy access

Refrigerant control

Electronic expansion valve

Operation sound (Hi / Me / Lo)

dB-A

36 / 32 / 28

Refrigerant tubing connections

Flare type

Refrigerant tube di-

ameter

Liquid tube

in. (mm)

1 / 4 (6.35)

Gas tube

in. (mm)

1 / 2 (12.7)

Drain connection

13 A, OD 45 / 64”

Remote controller

Optional (RCS-TM80BG, RCS-SH1AAB)

Refrigerant tubing kit / Accessories

Optional / –

Color (Approximate value)

Munsell 3.0Y 8.6 / 0.8, RAL 9002-GL (resemblant color)

DIMENSIONS & WEIGHT

Unit dimensions

Package dimensions

Unit dimensions

Height

in. (mm)

11-7 / 32 (285)

13-21 / 32 (347)

Width

in. (mm)

39-3 / 16 (995)

41-15 / 16 (1065)

Depth

in. (mm)

8 (203)

10-1 / 4 (260)

Net weight

lbs. (kg)

31 (14)

Shipping weight

lbs. (kg)

35 (16)

Shipping volume

ft

3

(m

3

)

3.4 (0.096)

Rated conditions

Colling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB
Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB

TD831138-02_W-2WAY.indb 66

2007/07/26 14:33:08

Advertising
This manual is related to the following products: